DIN-rail mount form factor serial to Ethernet industrial device server with industrial protocols.
Specifications
Serial Interface:
Interface: RS-232, RS-422, or RS-485
Connector: Screw terminals or RJ45
Data Rates: 300 to 115,200 bps
Characters: 7 or 8 data bits
Parity: odd, even, none
Stop Bits: 1 or 2
Flow Control:
Software: XON/XOFF
Hardware: RTS/CTS
Installable Serial Protocols (XPress-DR-IAP only)
Network Interface:
Standards: ARP, UDP/IP, TCP/IP, ICMP, SNMP, BOOTP, DHCP, TFTP, Telnet, and HTTP
Interface: 10Base-T/100Base-TX Ethernet
Connector: RJ45
Installable application layer protocols (XPress-DR-IAP only)
Indicators: Ready, Fault/Configuration, Activity, Link, Serial Transmit Data, Serial Receive Data
Power:
Input: 9 to 30VDC/9-24VAC, 3W maximum
Connector: Screw terminals for power and ground
Environmental (Operating):
Temperature: 0° to 60°C (32° to 140°F)
Humidity: 20% to 90% RH, non-condensing
Mounting: DIN-rail (35 mm)
Material: High-impact plastic
Dimensions (L x W x H): 6.09 x 3.55 x 8.8 cm (2.4 x 1.4 x 3.5 in)